Engineering / Stair regulations in Europe / Netherlands

Engineering · Reference

Stair regulations in the Netherlands

The numbers that matter when you design a stair or balustrade in the Netherlands, from Besluit bouwwerken leefomgeving (Bbl).

· Source status: Official regulation texts

Requirements

Rail height on stairs≥ 850 mm (from the tread nosing) where the drop exceeds 1 m
Rail height on landings and balconies≥ 1000 mm; ≥ 1200 mm where the drop exceeds 13 m
Max opening in guarding≤ 100 mm up to 700 mm height (also in dwellings)
ClimbabilityNo footholds between 200 and 700 mm
RiseDwellings ≤ 188 mm; other uses ≤ 210 mm
GoingDwellings ≥ 220 mm; other uses ≥ 185 mm (on the walking line)
Stair width≥ 800 mm
HeadroomDwellings 2300 mm; other uses 2100 mm
Handrail800–1000 mm (stairs rising over 1 m and steeper than 2:3)
Handrail extensionIn certain buildings on both sides, continuing ≥ 300 mm horizontally (Bbl 4.28)
LandingsOne flight may rise no more than 4 m; above that an intermediate landing is required
NotesMax 50 mm between guarding and the edge of the floor or stair. The lowest 1 m of a stair needs no side barrier.

Summary for designers, last checked November 2026. Always confirm against the current official text and with the local building authority.

Questions and answers

How high must a stair balustrade be in the Netherlands?

Rail height on stairs: ≥ 850 mm (from the tread nosing) where the drop exceeds 1 m. Rail height on landings and balconies: ≥ 1000 mm; ≥ 1200 mm where the drop exceeds 13 m.

What is the maximum opening in stair guarding in the Netherlands?

Max opening in guarding: ≤ 100 mm up to 700 mm height (also in dwellings). Climbability: No footholds between 200 and 700 mm.

When does a stair need a landing in the Netherlands?

Landings: One flight may rise no more than 4 m; above that an intermediate landing is required.

Need a stair that passes first time?

Send us your drawings. We check them against the local rules, engineer the stair and build it in our Riga workshop.